Basic Info.
Type
Lithium-Ion Batteries
Usage
Car, Bus, UPS, Electric Power, Lighting, Electric Bicycle, Boat, Bess
Discharge Rate
High Discharge Rate
Shape
Cylindrical Battery
Operating Voltage Range
1164.8~1497.6 V
Max. Charge/Discharge Power
266.2kw (0.5cp)
Operating Ambient Temperature
-30c~55ºC
Ingress Protection Rate
IP54
Transport Package
Carton or Plywood
Specification
lifepo4 battery
Product Description
Product DescriptionCATL ESS C&I Product Introduction
Cabient Energy Storage System Solutions
Module & High Voltage Box
C&I Products- Module & HVB
Application:
· Modular, standard size and various interface, friendly for product integrators.
Compatibility design:
· The height of the module is 3U, and a 19-inch cabinet is used.
· Support max. 1500V application.
· Configurable modular design makes easy and flexible configurations.
· Multi comm . Ports and dry contact for system integration.
Design for e-maintenance:
· Modular pluggable BMS design for easy maintenance.
Simplicity:
· Neat appearance , Non-Exposed cables.
Module |
Items | Specifications |
Cell Type | LFP, 100Ah |
Connection | 2 parallel 16 series (2P16S) |
*Total Capacity/ Energy | 200Ah/10.24kWh |
"Usable/Capacity/Energy | 196Ah/10.03kWh |
*Nominal Voltage | 51.2V |
Output Voltage Range | 44.8~57.6V |
Max. Charge/Discharge Power | 5.12kW (0.5CP} |
*Room Temperature Cycle Life(25°C±2°C) | 8000cycles @60%S0H |
Room Temperature Calendar Life{25C±2°ºC) | 15 years |
Module Safety Certification | IEC62619 /1973/9540A/GBT36276/RCM/CE EMC/FCC |
UN Transportation Test Standard | UN38.3 |
Ingress Protection | IP20 |
Optimal operatingtemperature | 15C~30°ºC |
Operatingambient humidity | 5%~95%, No condensaticn |
Dimension | W445*D913.2*H129 mm(without bracket) |
Altitude | ≤3000m |
Weight | 80kg |
Installaticn | Rack-mounted installation |
HVB |
Items | C-H1500100SA1 |
Max. OperatingVoltage Range | Max. 1500V DC |
Max. Input/ Output current | 120A |
Optimal operating temperature | 15C~30ºC |
Environment temperature range | -10C~50°ºC |
Communication between HV-BOX and PCS | Ethernet |
Max. Module Serial Connect | 26S |
Max. Parallel | 32 |
Dimension | W442*D500*H217.2 mm |
Weight | 26kg |
HVB(High Voltage Box) is the interface with the external system, there only are three kinds of interface:
· Power connection with PCS: P+/P- 100A;
· Communication with EMS or PCS: Ethernet, Modbus TCP or CAN
· Aux. power comes from grid: 110VAC/220VAC, 100W;
Outdoor Battery Cabinet
DC Solution: 1000~1500V for medium scale project
Application:
· Support max. 4 cabinets in parallel, friendly for medium-sized project integrators.
DC side all-in-one design:
· Integrated with the battery module, HVB, Power distribution box, UPS,FFS, Air conditioner etc ., make up an complete DC side system .
Explosion prevention design:
· Equipped with gas detector and gas exhaust fan in accordance with NFPA69.
Parameters:
ltems | Specifications |
*Total capacity | 400Ah |
*Usable capacity | 392Ah |
*Total energy | 532.48kWh |
*Usable energy | 521.83kWh |
Nominal voltage | 1331.2V |
Operating voltage range | 1164.8~1497.6 V |
Max. Charge/Discharge power | 266.2kW (0.5CP) |
*Room Temperature Cycle Life(25ºC±2°ºC) | 8000cycles@60%SOH |
Room Temperature Calendar Life(25ºC±2ºC) | 15 years |
Operating ambient temperature | -30C~55ºC |
Optimal operating temperature | 15ºC~30ºC |
Operating ambient humidity | 5%~95%, No condensation |
*RTE | 294% for fresh battery |
Rack Parallel connection | Max. 4 units in parallel |
Ingress Protection rate | IP54 |
Anti-corrosivity Category | C3 |
Cooling | HAVC, cooling capacity:10kW for 0.5CP, |
Dimension | W2200mm*H2443mm*D1400mm |
Weight | 6000kg |
Altitude | 53000m |
Communication between PCS and battery system | Ehernet |
Regulation compliance | IEC62619 /1973/GB/T 36276/CE EMC/FCC, 9540A| |
EMC standard | EN61000-6-1&EN61000-6-3 |
UN Transportation Test Standard | UN3841(Sea) for bttery cabinet,UN38.3(Sea) for pack |
Environment protection standard | RoHS, REACH,TSCA, battery directive |
DC Solution: 1000~1500V for large scale project
Environment protection standard | RoHS, REACH,TSCA, battery directive |
Outdoor All-in-one Cabinet
All-in-one Design:
• Fully Integrated with battery rack, PCS, PV inverters, EMS and power distribution unit; (3*PWS2-30P-NA, 3*PDS1-60K)
• Modular design, flexible function configuration:30kW133kWh,60kW133kWh
• Support peak shaving, off-grid, Solar-Storage-Diesel mode;
• Wide voltage range: 150V~750V, capacity configurable;
• STS can be added to achieve seamless switching;
Parameters:
Model | SES-031-261 |
AC side data |
Nominal apparent power | 90kVA |
AC grid connection type | 3W+N |
Overload capability | 110%, continuous overloading |
Nominal AC voltage | 380/400/480 0(-15%~15%)Vac |
AC grid frequency | 50/60(-2.5~2.5) Hz |
THDi | ≤3% |
Power factor | -1~1 |
Battery side data |
Max. Charge/Discharge power | 99kW |
Voltage range (PCS) | 150~750(350~750 fullload) Vdc |
Max. current (PCS) | 3*90A |
Battery voltage range | 582.4/~748.8V |
Battery configuration | 2P16S*13S*2P |
Battery energy capacity | 266.24kWh |
PV side data |
Nominal power | 135kW |
MPPT range | 200V~810V |
MPPT branch | 9 |
System data |
Dimension (WXHXD) | 1600×2450×1100 mm |
Weight | 2350kg |
Noise level | <75dB |
Ingress protection class | IP54 |
Operating ambient temperature | -20~60°C(>45°C,derating) |
Cooling mode | HVAC |
Operating ambient humidity | 0~100% (no condensing) |
Altitude | 3000m(>3000m, derating) |
Communication data |
Interface | RS485, Ethernet, CAN |
Communication Protocol | Modbus TCP/RTU |
Containerized solution
Battery Cooling Mode
The container system is equipped with 2 HVACs the middle area is the cold zone, the two side area near the door are hot zone.
PCS cabin is equipped with ventilation fan for cooling.
Layout
40 foot Container can Installed 2MW/4.58MWh.
We will configure total 8 battery rack and 4 transformer 500kW per transformer each transformer will be provisioned 2 battery rack.
Please refer the 40 foot container battery system specification as follow.
Subsystem- Combiner cabinet ( 1500V ,2MW)
The combiner cabinet contains three parts:
· DC main circuit combination: combine several battery cabinets'main circuit, then connect to PCS;
· Aux.: Get electricity from grid, then supply to HVAC and BMS;
· COM: connect with PCS or EMS through Ethernet Switch;
Parameters:
Items | Specifications |
Rated voltage | 1500V |
Max.current/(@25°C) | 2*800A |
Peak current/(@25°ºC) | 2*944A@5s |
Number of connected battery cabinets | Max. 16 battery cabinets for0.25CP;8 battery cabinets for0.5CP; |
Communication port | Ethernet( Eight ports) |
Powerinterfacet to PCS | 2 positive and 2 negative ports, 6*Φ13 |
| Powerinterfacet to batterycabinets 2 positive and 2 negativeports, 4*48 |
Distribution portfromgrid | 80A,480VAC(Configurable),3P+N |
Distribution portto battery cabinets | 6*25A,220VAC, ForHVAC,P+N 2*10A,220VAC, ForBMS,P+N |
Dimensions(W*H*D) | 1800*2450*1000mm |
Weight | 1400kg |
Operating ambient temperature | -30C~55ºC |
Operating ambient humidity | 5%~95% |
Ingress Protectionrate | IP55 |
Cooling | Air forced cooling |
Altitude | <3000m |
Indoor product- Battery Rack
Parameters:
Items | 14 module | 12 module | 10 module |
Battery string configuration | (2P16S)*14S | (2P16S) *12S | (2P16S)*10S |
*Total capacity | 200Ah | 200Ah | 200Ah |
*Usable capacity | 196Ah | 196Ah | 196Ah |
*Total energy | 143.36kWh | 122.88kWh | 102.4kWh |
*Usable energy | 140 kWh | 120kWh | 100kWh |
Nominal voltage | 716.8V | 614.4V | 512V |
Operating voltage range | 627.2~806.4V | 537.6~691.2V | 448~576V |
Max. Charge/Discharge power | 71.68 kW (0.5CP) | 61.44kW (0.5CP) | 51.2kW |
Peak charge/discharge power | 84 KW/5S | 72KW/5S | 60KW/5S |
*Room Temperature CalendarLife(25C±2ºC) | 15years | 15 years | 15years |
*Room Temperature Cycle Life(25C±2°ºC) | 8000cycles@60%S0H | 8000cycles@60%S0H | 8000cycles@60%S0H |
Operating ambient temperature | -10C~50ºC | -10C~50ºC | -10C~50ºC |
Optimal operating temperature | 15C~30ºC | 15C~30ºC | 15C~30ºC |
Operating ambient humidity | 5%~95%, No condensation | 5%~95%, No condensation | 5%~95%, No condensation |
*RTE | 294% for fresh battery,0.5CP discharge/charge 25C | 294% for fresh battery, 0.5CP discharge/charge 25C | 294% for fresh battery, 0.5CP discharge/charge 25ºC |
Discharge rate of Module | <2%/month/@25ºC | <2%/month/@25ºC | S2%/month/@25ºC |
Rack Parallel connection | Max. 16 units in parallel | Max. 16 units in parallel | Max. 16 units in parallel |
Dimension | 550mm*920mm*2300mm | 550mm*920mm*2300mm | 550mm*920mm*2300mm |
Ingress Protection rate | IP20 for module and HV BOX | IP20 for module and HVBOX | IP20 for module and HVBOX |
Cooling | Natural air cooling | Natural air cooling | Natural air cooling |
Altitude | ≤3000m | ≤3000m | ≤3000m |
DC Solution: 750~1000V
Remove 9 battery modules each string to match 750V~1000V voltage range application.
Certification: Other than 9540A,UN 38.3 and EMC, other certification.
Support max. 4 cabinets in parallel, friendly for medium-sized project integrators.
Parameters:
Items | Specifications |
*Total capacity | 400Ah |
*Usable capacity | 392Ah |
*Total energy | 348.16kWh |
*Usable energy | 341.19kWh |
Nominal voltage | 870.4V |
Operating voltage range | 761.6~979.2 V |
Max.Charge/Discharge power | 174.08kW (0.5CP) |
*Room Temperature Cycle Life(25ºC±2ºC) | 8000cycles@60%SOH |
Room Temperature Calendar Life(25C±2ºC) | 15 years |
Operating ambient temperature | -30C~55ºC |
Optimal operating temperature | 15ºC~30ºC |
Operating ambient humidity | 5%~95%, No condensation |
*RTE | ≥94% for fresh battery |
Rack Parallel connection | Max. 4 units in parallel |
Ingress Potection rate | IP54 |
Anti-corrosivity Category | C3 |
Cooling | HAVC, cooling capacity: 6kW for 0.5CP, |
Dimens ion | W2200mmH2443mm*D1400mm |
Weight | 4600kg |
Altitude | 53000m |
Communication between PCS and battery system | Ethernet |
Regulation compliance | IEC62619 /1973/GB/T 36276 |
EMC standard | EN61000-6-1&EN61000-6-3 |
UN Transportation Test Standard | UN38.3(Sea) for pack, |
Environment protection standard | RoHS,REACH,TSCA, battery directive |
Company Introduction
EVL Battery Limited is a leading NCM Lithium Battery manufacturer from China and its public company in the Hongkong Stock Exchange
market. There are 4 factories in Fujian and Guangdong. The production capacity of 4 factories is as much as 20 GWh per year. EVL Battery
Limited is the number one Lithium Battery manufacturer from China.
Our Services & Strength
We provide high-quality EVL Battery to clients all over the world and help clients deliver batteries from China to them by sea and by air at a
reasonable price. And we provide the necessary technical support and warranty to you!
FAQ
Q: What is the life expectancy of a Lithium battery?
A: The typical estimated life of the Lithium Iron Phosphate (LiFePO4) battery is 5-15 years or 2000 to 8000 charge cycles. One charge cycle
is a period of use from fully charged, to fully discharged, and fully recharged again.
Q: If I want to charge a solar LiFePO4/Lithium Ion battery, which already has PCB, would a normal SLA controller work fine?
A: For LiFePO4 / Lithium-Ion battery, we always recommend using the LiFePO4/Lithium-Ion solar controller. Especially if you are using the battery
as UPS (backup power supply). The Lead-Acid solar controller will constantly provide pulse current to the battery, in the long run, it might
damage the PCB. So the PCB won't be able to protect the battery when it should be.
Q:I am a distributor. Can I cooperate with the battery warehouse for a long time?
A: Yes, Individual pricing for large scale projects and wholesale demand is available
Q: Why hasn't my ups or FedEx transportation number been updated?
A: This is normal, in countries with tariffs, our packages need to pass the customs of your country before they can be delivered to the local
UPS or FedEx. Once they pass the customs and update the transportation number, you can usually receive the goods within 3-5 days.
Q: Are the cells I bought balanced?
A:We know the importance of maintaining the consistency of each cell in the battery pack, so we will match and balance all cells to ensure
that the internal resistance, voltage, and capacity of cells are completely matched and balanced before delivery. This process is very necessary.
Address:
Huang He Road, Xuecheng District, Zaozhuang, Shandong, China
Business Type:
Trading Company
Business Range:
Electrical & Electronics, Service
Management System Certification:
ISO 9000
Company Introduction:
A professional and reliable shopping center providing Thunder Sky Winston Battery, LiFePO4 Battery, Lithium Iron Phosphate Battery, CALB, Sinopoly Battery, Headway Battery, TC/Elcon charger, Kelly controller and Ligoo BMS at reasonable prices and shipping them globally.
EVLithium was established in 2007, which aims to provide full power solution for people who are building their electric vehicles and who want a real electric vehicles and lithium battery pack for storage energy project. Evlithium is becoming one of leading lithium iron phosphate battery supplier from China. With over 10 years friendly cooperation Winston Battery Limited, Evlithium is official leading dealer of Winton battery and provide local service in Europe, North America and Australia. Our Headquater in Hong Kong and production facilities located in Shandong province, People Republic Of China. We start our new business of Chemisty (Oxalic Acid) since 2015, we have invested a Chemistry facoty in Shandong province, North of China. Its the second largest Oxalic Acid producer all over the world. We provide high quality Oxalic Acid with reasonable price and deliver them to all over the world.